This is plc function that we can change between normal open and normal close,
For example: Auto Lube is wired signal normal close. If you wire normal open, the control Centroid will show alarm “ Low Lube” you have to add 1 to value of parameter 178.
LubeNONC IS MEM200 ; P178 Bit 0 (1)
SpindleNONC IS MEM201 ; P178 Bit 1 (2)
AirSignalNONC IS MEM202 ; P178 Bit 2 (4)
ToolCounterNONC IS MEM203 ; P178 Bit 3 (8)
ServoFaultNONC IS MEM204 ; P178 Bit 4 (16)
ZeroSpeedNONC IS MEM205 ; P178 Bit 5 (32)
OrientCompleteNONC IS MEM206 ; P178 Bit 6 (64)
;NoReverseSpindle IS MEM207 ; P178 Bit 7 (128)
ReverseClamp IS MEM208 ; P178 Bit 8 (256)
SpinRangeNONC IS MEM209 ; P178 Bit 9 (512)
ChillerFaultNONC IS MEM210 ; P178 Bit 10 (1024)
DoorSWNONC IS MEM211 ; P178 Bit 11 (2048)
ToolThruNONC IS MEM212 ; P178 Bit 12 (4096) /ATC Lock NONC for Lathe .
;uP178Bit13 IS MEM213 ; P178 Bit 13 (8192)
;uP178Bit14 IS MEM214 ; P178 Bit 14 (16384)
;uP178Bit15 IS MEM215 ; P178 Bit 15 (32768)